Patch-type thermal aerosol fire suppression device
Keywords:
Category:
Detailed Description
Product Overview of Potted Thermal Aerosol Fire Extinguishing Devices
I. Scope of Application:
This specification applies to the brand and model manufactured by our company. QRR0.012G/S-ZY, QRR0.03 G W / S -ZY,QRR0.01GW/S-ZY,QRR0.06GW/S-ZY Type aerosol fire-extinguishing device.
II. Content and Explanation:
This product specification defines the product’s technical requirements, test methods, marking, labeling, packaging, and transportation.
Transmission and storage requirements. This specification applies to design qualification and shipment inspection, as well as production inspection and type… formula Inspection and
During quality consistency verification, it serves as the basis for quality appraisal and inspection.
III. Reference Standards:
GB50370-2005 Code for Design of Gas Fire-Extinguishing Systems
GA 499.1-2010 Aerosol fire suppression system The 1 Section: Thermal Aerosol Fire Extinguishing System
GB50116-2008 Code for Design of Automatic Fire Alarm Systems
GB7258—2012 Technical Requirements for the Safe Operation of Motor Vehicles
GBT3730.1-2001 Terms and Definitions for Vehicle and Trailer Types
GBT15089-2001 Classification of Motor Vehicles and Trailers
IV. Product Features:
This device employs gas‑based fire suppression technology. Developed through extensive experimentation in accordance with national and industry standards, it is tailored to the specific environmental conditions of automotive engine compartments, electric vehicle battery compartments, high‑ and low‑voltage switchgear cabinets, bank ATMs, and similar spaces. It delivers exceptionally robust automatic fire‑extinguishing performance, effectively preventing fires in enclosed or semi‑enclosed areas. Product.
V. Product Features:
5.1 The extinguishing agent of a thermal aerosol fire suppression system is a solid energetic chemical substance, classified as a pyrotechnic composition.
By initiating the activation of the extinguishing agent through an oxidation–reduction process, a chemical reaction is triggered, generating a large volume of inert gas,
5.2 The fire-extinguishing mechanism of automatic fire suppression systems combines physical, chemical, and vapor‑cooling extinguishing methods. The total flooding fire suppression method employed:
a , by physically diluting oxygen in the air “ Asphyxiation fire suppression ” As the primary method, it interrupts the flame’s reaction chain.
Chain‑reaction inhibition disrupts the combustion conditions at the fire scene, rapidly reducing the concentration of free radicals.
b 、 There exists a chemical fire-extinguishing method that inhibits the progression of chain‑reaction combustion.
c , Condensation and vaporization of water vapor lower the temperature of the burning material.
5.3 The aerosol (smoke) generated after the fire suppression system is activated is non-toxic, environmentally friendly, non-corrosive, and does not deplete the atmospheric ozone layer. ODP The value is 0, GWP The value is close to 0 );
5.4 The fire suppression system, when networked with the fire alarm control panel, enables high-speed, highly efficient, and comprehensive fire suppression.
5.5 • Supports multiple devices connected to the network via wired connections, ensuring that the protected area is not affected by cable length.
5.6 The system features a pipeless design and requires no pressure vessels, actuators, valves, or piping, thereby reducing both the footprint and project costs.
5.7 The fire‑extinguishing system features solid‑state storage with no leakage, operates at atmospheric pressure, and is safe, reliable, and easy to store and transport.
5.8 , Scope of Application
The thermal aerosol system is a total flooding system, suitable for extinguishing fires in relatively enclosed spaces. A 、 B Class fires and
Initial-stage fire involving electrical cables.
a , extinguish A Class A fires: such as initial fires involving solid materials like wood and paper, are suitable for wood product warehouses,
Archives, museums, libraries, information centers, and similar facilities;
b. Extinguish B Class of fires: Applicable to the production, use, or storage of diesel fuel ( -35 (excluding No. diesel), heavy
Fires in areas containing Class C flammable liquids, such as oil, transformer oil, animal fats, and vegetable oils;
c. Extinguishing Electrical Cable Fires: Suitable for transformer (distribution) rooms, generator rooms, cable trenches, and cable areas.
Fires in wells, cable trenches, computer rooms, telecommunications rooms, and similar facilities.
5.9、 Scope of Non-Applicability
Automatic thermal aerosol fire suppression systems shall not be used to extinguish fires involving the following substances:
a Chemical substances that can rapidly oxidize even in the absence of air, such as nitrocellulose and gunpowder.
b , reactive metals such as potassium, sodium, magnesium, titanium, zirconium, uranium, and plutonium.
c Compounds that can decompose on their own, such as certain peroxides and hydrazine.
d , metal hydrides, such as potassium hydride and sodium hydride, etc.
e , able to self Burn Substances such as phosphorus.
f , strong oxidizing agents, such as nitrogen oxides and fluorine.
5.10、 Inapplicable Locations
a , commercial establishments, food and beverage services, entertainment venues, and other densely populated areas ;
b , Areas for storing flammable and explosive materials.
Six , Performance Parameters:
Serial number | Project | Parameter |
1 | Operating temperature environment | -5 0℃ ~ +9 5℃ |
2 | Operating humidity range 境 | ≤95% |
3 | Appearance dimensions | phi 60mm*30mm |
4 | Materials | Metal casing material |
5 | Fire-extinguishing gas release Time | ≤ 40 S |
6 | Thermal spacing | 0.35 m Time ≤ 400 °C |
7 | Applicable Space | ≤ 0.5 cubic meter |
8 | Fire suppression system activation temperature | 170 °C |
9 | Fire suppression system activated Lagging behind Time | ≤5 S |
10 | Firefighting time | ≤ 40 S |
11 | Fire extinguishing agent weight | 30 ±2% g |
12 | Use of fire suppression systems Validity period | 10 year |

VIII. Design Requirements
8.1 , System Settings
a 、 The protected area shall be delineated as a fixed, enclosed space, in order to cubic meter For calculation purposes;
b , More than one prefabricated fire-extinguishing system unit is installed within the same protected zone. 1 At the time, it must be capable of starting simultaneously, and its…
When responding Poor shall not Greater than 2s;
c The protected volume of a single pre-engineered aerosol fire suppression system shall not exceed 0.5 cubic meter ; Set multiple units
During installation, the distance between them shall not exceed 1 m ;
8.2 , Thermal aerosol pre-engineered fire suppression system
a The design extinguishing density of a pre‑engineered aerosol fire‑extinguishing system shall not be less than the density of… 1.3 Times.
b , the extinguishing density of thermal aerosol is 100g/ m 3.
c , electrical equipment fires in locations such as telecommunications equipment rooms and computer rooms, Set The mass density shall not be less than
130g/ m 3 。
d For fires in cable tunnels (including mezzanines and shafts) and in standby generator rooms, the design aerosol density shall not be less than…
at 140g/ m 3。
e In protected areas such as telecommunications equipment rooms and computer rooms, the extinguishing agent discharge time shall not exceed 90s, In
In other protected areas, the discharge time shall not exceed 120s。
f The extinguishing concentration of aerosol agents for other combustible materials shall be determined by testing.
g The fire‑extinguishing impregnation time shall comply with the following provisions:
( 1 ) For fires involving solid surfaces such as wood, paper, and fabrics, the following should be used: 20min。
( 2 ) For fire protection zones such as telecommunications equipment rooms and computer rooms, as well as other solid-surface fires, the following measures shall be adopted:
Use 10min。
( 3 ) The impregnation time for fire suppression in other protected zones using thermal aerosols shall be determined by testing.
h The design quantity shall be calculated according to the following formula:
W=C 2 ×V×K V
In the formula W— Design quantity of fire extinguishing agent ( kilogram ); C 2 — Fire-extinguishing design density (kg/ m3 )
V— Net volume of the protected area ( m3 ) K V --- Volume correction factor.
V < 500 m 3, K V =1.0 ;500 m 3 ≤V < 1000 m 3, K V =1.1 ; V≥1000 m 3, K V =1.2
9. Life Testing
The test life of the fire-extinguishing device is determined using the modified Arrhenius equation ( Arehenius ) Equation, see
Formula ( 1 ), the storage life at room temperature is estimated based on the test duration under high-temperature conditions.
t 0 = τ·t 1 ……………………………………………… ( 1 )
In the equation:
t 0 —— Room temperature ( +21°C ) Storage time, in days ( d );
t 1 —— High temperature ( +71℃ ) Test duration, in days ( d );
tau —— Acceleration coefficient.
tau According to equation ( 2 ) Calculate:
τ=r (T 1-T0 )/A ……………………………………………… ( 2 )
In the equation:
r —— The temperature coefficient of the reaction rate is taken as r=2.7;
T 1 —— High-temperature test temperature, in units of kelvins ( K );
T 0 —— Storage temperature at room temperature, in kelvins ( K );
A —— The temperature change constant corresponding to the reaction temperature coefficient is taken as A=10K 。
After the high-temperature test, by ( 1 ) Calculate the storage duration of the fire-extinguishing device at ambient temperature.
For example: High-temperature test temperature T 1 For 24673.5K , that is 90℃ ;
By calculation: number of days stored at room temperature t 0 For 3661 d , that is 10 year 。
Patch-Type Thermal Aerosol Fire Suppression Device | Frequently Asked Questions
Q1: What scenarios are suitable for surface‑mounted aerosol fire suppression devices?
A1: Suitable for use in confined, enclosed enclosures such as switchgear cabinets, energy storage battery cabinets, and communication cabinets to extinguish initial electrical fires inside; not suitable for fires involving reactive metals.
Q2: Why is it called “surface-mount”? Is it easy to install?
A2: Featuring a thin, surface-mount design, it can be adhered directly to the inner wall of the cabinet without the need for drilling or welding. Its compact, lightweight installation saves space and is compatible with both new and existing cabinet retrofits.
Q3: What startup methods are available for the device?
A3: Supports automatic start-up via temperature control and can also be connected to a fire alarm system to enable interlocked activation through electrical signals.
Q4: Does the discharge leave any residue, and could it damage electrical components?
A4: After extinguishing the fire, solid particulate residues remain and must be cleaned up; it is not recommended for use with ultra‑high‑precision, cleanroom electronic equipment.
Q5: How long is the product’s shelf life, and is regular hydrostatic pressure testing required?
A5: The agent typically has a shelf life of 5 years. It is a single-use fire-extinguishing device, does not contain a pressure vessel, and therefore does not require hydrostatic testing of the cylinder. Upon expiration, the entire unit must be replaced.
Q6: Can it be reused?
A6: Not reusable; once the discharge is triggered, the device becomes inoperative and must be replaced with a new unit.
Q7: Is the temperature high during discharge, and could it ignite nearby cables?
A7: The product is equipped with a built-in cooling system. During installation, ensure compliance with relevant standards by maintaining adequate safety clearances and keeping it away from flammable components.
Q8: Can it start normally in low-temperature environments?
A8: The product can reliably start within its rated operating temperature range; exceeding this range may degrade start-up performance.
Q9: Can the device be disassembled privately?
A9: Disassembly is strictly prohibited; the device contains pyrotechnic materials, and disassembly poses risks of ignition and deflagration.
Q10: What items should be inspected during routine maintenance?
A10: Regularly inspect the enclosure for damage or detachment, verify that the wiring is intact, and confirm that the product is within its expiration date.
Related Products
Inquiry Price