Single-cabinet-type heptafluoropropane fire suppression system

Fire classes that can be extinguished: solids, liquids, gases, and energized electrical fires.

Category:

Telephone:

Detailed Description

Product Overview of Cabinet-Type Heptafluoropropane Fire Extinguishing Systems

One Overview and Scope of Application

 

1 Introduction to Fire Extinguishing Systems

 

Heptafluoropropane ( HFC-227ea ) is a clean‑gas fire suppressant that extinguishes fires through a chemical mechanism. It is colorless, odorless, low‑toxicity, non‑conductive, and does not contaminate the protected object. In particular, it has no adverse impact on the atmospheric ozone layer. , ( ODP With a zero ozone depletion potential, it meets environmental protection requirements and represents a relatively ideal alternative to halon fire‑extinguishing agents at this stage. This extinguishing agent boasts high extinguishing efficiency, rapid action, and no secondary pollution. The cabinet‑type heptafluoropropane fire‑extinguishing system is a prefabricated, mass‑produced solution. It is a pipeless, lightweight, mobile, automatic fire‑suppression device that offers flexible and convenient installation as well as an aesthetically pleasing appearance. Moreover, it eliminates pipeline losses, delivers high extinguishing efficiency with swift response, and leaves no environmental contamination. In the event of a fire, it can automatically discharge the extinguishing agent directly into the protected area, providing a quick and hassle‑free solution.

 

This fire suppression system does not include a dedicated cylinder room; the gas cylinders and the entire system are installed within the protected area. It is suitable for small‑area protected spaces such as computer rooms, archives, vaults for valuable items, and telecommunications centers. Multiple cabinet‑type heptafluoropropane gas fire suppression units can also be interconnected to protect larger areas. The system can be integrated with a fire control center or equipped with an independent automatic fire suppression controller, forming a self‑contained solution that offers users convenient and flexible options. For existing buildings requiring the addition of a fire suppression system, cabinet‑type heptafluoropropane units are a particularly appropriate choice.

 

2 , Characteristics of the extinguishing agent

 

1 ) is a colorless, odorless gas with an ozone depletion potential ( ODP ) for  0 , it meets environmental protection standards and is ideal.

 

Alternative to dragon fire extinguishing agent;

    2 ) It extinguishes fires through both physical and chemical mechanisms, serving as a new-generation, highly efficient, low-toxicity fire suppressant. It requires a low extinguishing concentration, uses fewer cylinders, and occupies minimal space.

 3 ) Heptafluoropropane fire suppressant is non-conductive and water-free, and will not damage electrical equipment, magnetic tapes, documents, or other materials.

 4 ) The minimum design concentration is 7.35% ( V/V );

5 ) The highest concentration with no toxic effects ( NOAEL ) for  9% ( V/V ) Can be used in occupied areas.

 

3 , Applicable Scenarios

 

1 ) Can be extinguished A 、 B 、 C Various types of fires can be safely and effectively extinguished in occupied spaces.

 2 ) In areas where, after the release of the agent, no trace should remain or where cleaning up residues is difficult;  

3 ) The protected area contains valuable items, priceless treasures, precious archives, as well as software and hardware;  

4 ) Particularly suitable for: telecommunications main control rooms, airport control rooms, bank vaults, archives, libraries, computer rooms, and similar environments.

 

4 , inappropriate for the occasion

 

1 ) In situations involving chemical substances such as nitrocellulose and black powder, which can undergo rapid oxidation even in the absence of air;

 

2 ) Reactive metal —— Storage and production facilities for potassium, sodium, magnesium, titanium, and uranium;

 

3 ) Storage location for metal hydrides.

 

II. Flowchart of the Fire Extinguishing System Operation

Figure 1 Flowchart of the Cabinet-Type Heptafluoropropane Gas Fire Suppression System

III. Composition and Technical Parameters of the Fire Extinguishing System

1 , Composition of Cabinet-Type Heptafluoropropane Gas Fire Extinguishing System

The cabinet-type heptafluoropropane fire suppression system consists of fire detectors, an automatic alarm control panel, a fire suppression control panel, and the fire suppression unit itself (see figure). 2 ). This fire suppression system is an independent total flooding system, with one or several pipeless units serving a single protected area.

This device is equipped with automatic, manual, and mechanical emergency‑manual drive modes.

Figure 2  User‑supplied alarm control panel–based pipeless automatic fire suppression system

 

Schematic Diagram of the Cabinet-Type Heptafluoropropane Gas Fire Extinguishing System : (See figure) 3 )

(See figure) 3 )

2 Technical Specifications

2 . 1 Technical Parameters of the Fire Extinguishing System

Technical Parameters of the Fire Extinguishing System   Table 1

Model number

GQQ Type

Drive method

Electric and mechanical manual drive

DC24V

Form

Fixed type

Pneumatic and mechanical manual actuation

≤ 150N

Work stress

2.5 MPa ( 20 °C)

Drive delay

0 ~ 30s

Ambient temperature

0 °C~ +50 °C

Fire suppression system discharge time

≤ 10s

 

2 ) Technical Parameters of a Single-Cabinet Heptafluoropropane Gas Fire Suppression System

Technical Parameters of the Fire Extinguishing System   Table 2

Type    Number

Storage bottle

Regulation   grid

Storage bottle

Quantity

Injection time

( s )

Spray   Shoot   after

Extinguishing agent remaining quantity

( Kilogram )

External dimensions (mm)

(long * wide * High)

GQQ40/2.5-ZY

40L

1

≤10s

0 ~ 3

500*43 0 *1 200

GQQ70/2.5-ZY

70L

1

0 ~ 3

500 *43 0*1400

GQQ90/2.5-ZY

90L

1

0 ~ 3

500 *43 0 *1 700

GQQ 100/2.5-ZY

100L

1

0 ~ 3

500 *43 0 *1 700

GQQ120/2.5-ZY

120L

1

0 ~ 3

500 *430*1900

GQQ150/2.5-ZY

150L

1

0 ~ 3

520 *50 0 *1900

GQQ180/2.5-ZY

180L

1

0 ~ 3

520 *50 0*2100

 

2.1 Fire extinguishing agent cylinder assembly

1) Purpose

It stores the extinguishing agent under normal conditions; in the event of a fire, the container valve activates to release the extinguishing agent.  

2) Composition

It consists of a fire-extinguishing agent, an gas cylinder, a container valve, a pressure gauge, a safety relief device, a siphon tube, and other components.  

3) Main performance parameters:  

Model Specifications

QMP2.5/40-ZY

QMP2.5/70-ZY

QMP2.5/90-ZY

QMP2.5/100-ZY

QMP2.5/120-ZY

QMP2.5/150-ZY

QMP2.5/180-ZY

Cylinder volume

40L

70L

90L

100L

120L

150L

180L

Operating temperature range

0 °C ~+50℃

Storage pressure

2.5MPa

Maximum working pressure

4.2MPa

Safely release pressure

5.9 ± 0.295MPa

Maximum filling density

1120 kg/m³

1000 kg/m³

1120 kg/m³

1000 kg/m³

1120 kg/m³

 

4) Operating Principle  

In the event of a fire, the electromagnetic actuator opens the container valve, allowing the extinguishing agent to be discharged from the valve and conveyed through a metal hose to the nozzle, where it is released into the protected space.  

5) Features  

a. The cylinder assembly is equipped with a safety relief device to prevent hazards caused by excessive pressure inside the extinguishing agent storage cylinders.  

b. The entire apparatus features a well‑designed, safe, and reliable structure, with straightforward maintenance.  

c. The extinguishing agent can be refilled multiple times.  

6) Installation, Usage, and Maintenance Instructions and Precautions  

a. During transportation and installation, the extinguishing agent cylinder assembly should not have the solenoid‑actuated actuator mounted on the container valve first, to ensure safety; handle with care, avoid impacts, and keep out of direct sunlight.  

b. The extinguishing agent cylinder assembly shall be securely mounted on the extinguishing agent cylinder rack.  

c. After the installation of the electromagnetic actuator, the container valve shall be equipped with both automatic and mechanical emergency activation modes.  

d. The pressure within the cylinder assembly must remain within the green zone of the pressure gauge. If the pressure falls below the lower limit of the green zone, the cause of the leak must be identified and the system recharged.  

e. The design, manufacture, acceptance, use, and periodic inspection of fire-extinguishing agent cylinders shall be conducted in accordance with the provisions of the current “Safety Technical Supervision Regulations for Gas Cylinders.”  

f. After the extinguishing agent has been discharged, the container valve shall be reset and the working diaphragm replaced by the manufacturer or a qualified professional company. The extinguishing agent shall then be recharged to the design‑specified charge.  

h. Maintenance and management shall be carried out in accordance with the requirements of GB 50263-2007, “Code for Construction and Acceptance of Gas Fire‑Extinguishing Systems.”

2.3 Nozzles and Fittings:

1) Purpose  

The cabinet nozzle is a total‑flooding nozzle, mounted at the top of the cabinet to discharge the extinguishing agent.

2) Composition

Made of copper alloy.

3) Main performance parameters:

Model Specifications

QPT40#/32

QPT52#/40

QPT63#/50

Single-hole diameter

Phi 9

Phi 12

Phi 14

Number of boreholes

12

12

12

4) Operating Principle  

By means of internal pressure, the gas inside is forced into the nozzle, where it atomizes the extinguishing agent through the nozzle orifice, ensuring uniform distribution throughout the protected area.

5) Features  

a. The entire apparatus features a well‑designed, safe, and reliable structure, with straightforward maintenance.

b. Can be reused multiple times.

6) Installation, Operation, and Maintenance Instructions and Precautions

a. The nozzle is mounted on the top of the housing and connected to the high-pressure hose.

b. Each nozzle must be fitted with a rubber gasket to prevent pressure leakage.

2.4 Electromagnetic Actuator

1) Working Principle

In the event of a fire, the DC power output by the fire alarm control panel activates an electromagnet, which in turn releases the actuating mechanism, causing the operating mechanism to function. This action punctures the sealing disc of the actuator valve or container valve, thereby opening the valve and releasing the control gas or extinguishing agent.

2) Structure

It consists of an electromagnet, a release mechanism, and an actuation mechanism.

3) Main performance parameters:

Type   Number

Stroke length

Start interface connection thread

Electricity      Magnetism      Iron

Type    Number

Rated suction power

Operating voltage / Electric current

DQ90N-ZY

≥ 8mm

M16×1.5

MFZ11-90

90N

DC 24V/ ≤ 1.8A

In an emergency, you can pull the safety‑lock lever with your finger to disengage the lock, then strike the manual button to activate the drive valve or container valve.

Special note: After the electromagnetic actuator has passed inspection, the spring in the operating mechanism is already compressed. To prevent unintended operation during installation, commissioning, and transportation, the operating mechanism is secured by a safety locking pin. Once the entire system has been installed and commissioned and is ready for service, the safety locking pin must be unscrewed, reversed, and securely reinstalled; otherwise, the electromagnetic starter’s operating mechanism will fail to function.

2.5 Cabinet:

The enclosure is fabricated from Q235 steel plate, with an electrostatic powder-coated finish in camel gray (custom colors are available upon request).

The cabinet is designed to house and secure components such as storage cylinders, high-pressure hoses, actuation devices, and cabinet-mounted nozzles. The bottom of the cabinet features anchor bolt holes for mounting, while the top is equipped with cable entry ports for connecting external equipment.

 

2.6 Signal Feedback Device

2.6.1 Purpose

The pressure signal generator is a component that feeds back the signal indicating the opening of a container valve or selector valve in the system to the automatic control section.

2.6.2 Composition

It consists of a valve body, a microswitch, a spring, a piston, and other components.

2.6.3 Application Requirements

Prior to installation, perform a functional check: when supplied with 0.75 MPa of compressed air, the pressure actuator shall operate, and after activation, it must be manually reset.

2.6. Main Performance Parameters:

Type   Number

Design pressure

Action pressure

Micro switch

Interface thread

Voltage

Electric current

QXF0.75/5.3-ZY

5.3MPa

0.75±0.075 MPa

DC24V

2.0A

R1/4

 

IV. Equipment Installation and Commissioning

1) Place the GQQ series cabinet-type heptafluoropropane gas fire suppression system securely on the designated installation location and ensure it remains firmly fixed.

2) Connect the electromagnetic actuator and the signal feedback device to the fire suppression control panel, and verify that the wiring is correct. For systems equipped with an automatic fire suppression alarm control panel, the user shall perform the wiring in accordance with the wiring diagram provided on the control panel.

3) Commissioning of the fire suppression system.

4) After the fire suppression system has been commissioned and is ready for operation, set the electromagnetic actuator to the ready‑to‑fire state (for detailed instructions, refer to the section on electromagnetic actuators at the end of this chapter).

V. Use and Operation of Fire Extinguishing Equipment

1. Automatic Control: When the protected area is unoccupied, set the control mode selector switch in the fire suppression control panel to the “Automatic” position, placing the fire suppression system in automatic control mode. If a fire occurs in the protected area, the fire detectors will transmit a fire signal, triggering the alarm to emit both audible and visual alerts and simultaneously issuing interlock commands to shut down associated equipment. After an approximately 30-second delay—during which all personnel must evacuate the protected area—the fire suppression command is then issued.

The electromagnetic actuator activates to open the container valve, allowing the extinguishing gas from the cylinder bank to be discharged through a high-pressure hose and deliver the extinguishing agent for fire suppression.

2. Electrical Manual Control: When personnel are working or on duty in the protected area, set the control mode selector switch inside the control cabinet to the “Manual” position, thereby placing the fire suppression system in manual control mode. If a fire occurs in the protected area, press the manual start button on the controller, or open the manual control box located outside the protected‑area door and press the start button inside; the fire suppression system will then be activated according to the procedure described above. Even when the system is in automatic control mode, electrical manual control remains available. Prior to initiating electrical manual control, all personnel must evacuate the protected area.

3. When a fire alarm is triggered, if it is determined during the delay period that there is no need to activate the fire suppression system, the red emergency stop button on the control panel or in the manual control box can be pressed to prevent the issuance of the fire suppression command and halt the system’s extinguishing sequence.

4. Before initiating fire suppression, all personnel must evacuate the protected area; after releasing heptafluoropropane, the required extinguishing soak time must be maintained before re-entering the protected area.

Ensure adequate ventilation by opening windows and doors; personnel shall not enter the protected area until ventilation has been completed, and if entry is unavoidable, they must wear a gas mask.

5. When it is necessary to test the system without discharging the extinguishing agent, press the test button on the operation‑test selector switch to perform the system test.

6. After this device has been used for fire suppression, the components listed below must be returned to their original positions before it can be reused:

(1) Reset the fire suppression controller (see the electrical operating manual);

(2) The piston of the signal feedback device returns to its original position;

(3) Reset the electromagnetic actuator;

(4) Replace the sealing diaphragm of the container valve.

VI. Maintenance and Servicing of Fire Extinguishing Systems

To ensure operational reliability, a comprehensive system for equipment inspection and maintenance shall be established in accordance with applicable regulations, operating procedures shall be developed, and qualified personnel shall conduct regular inspections of the equipment and maintain detailed records.

During maintenance and servicing, all operations must be carried out in strict accordance with the relevant provisions of GB 50263-2007, “Code for Construction and Acceptance of Gas Fire‑Extinguishing Systems.”

1. Daily (runtime) maintenance and upkeep

1) Keep the protected area and the control room clean, dry, and well-ventilated.

2) The surfaces of the fire suppression system and the fire alarm control panel are clean and free of dust.

3) The drive’s shear pins and lead seals shall be intact and undamaged.

4) Inspect the equipment’s nameplate and warning signs to ensure they are undamaged and clean and easily visible.

2. Quarterly maintenance and servicing

1) Check the pressure of each fire-extinguishing agent storage cylinder; the pressure gauge reading should be within the green zone.

2) Conduct a visual inspection of all system components, including fire‑extinguishing agent storage cylinders, container valves, actuators, high‑pressure hoses, nozzles, pressure transducers, and pressure gauges. The components shall show no deformation caused by impact or other mechanical damage; their surfaces must be free of rust, with the protective coating intact; nameplates must be legible; and protective covers, lead seals, and safety signs must be complete. If any of these conditions are found, the affected components shall be promptly replaced or repaired.

3. Annual maintenance and servicing

1) The opening conditions of the protected area, its intended use, and the types, quantities, and distribution of combustible materials shall comply with the design specifications.

2) Conduct a comprehensive inspection of the fire suppression system: Ensure all components are securely connected with no looseness; verify that the extinguishing agent delivery piping and nozzle orifices are free of blockages, and perform thorough cleaning of the system.

3) Conduct simulated alarm and activation tests on the fire‑alarm and extinguishing control panel; the signals and actions related to fire detection, alarm, and fire‑extinguishing control shall function normally. Verify the automatic and manual operating modes of the actuating device, including emergency start and emergency stop; the device shall operate as specified.

Remember: During simulation tests, the electromagnetic actuator must be removed from the container valve.

3) Remove the pressure transmitter for inspection; manually push the piston (to simulate the pressurization associated with agent discharge). The discharge indicator light shall illuminate, the signal shall be properly transmitted, and the system shall be capable of manual reset.

VII. Safety Usage Requirements

1) During transportation, fire-extinguishing devices shall be handled with care; impact, horizontal placement, or inversion is strictly prohibited.

2) Fire-extinguishing agent storage cylinders should be kept away from heat sources, protected from direct sunlight, and stored in a dry, well-ventilated area.

3) During disassembly and assembly, avoid damaging the device’s surface to prevent compromising its appearance.

4) Unauthorized personnel are prohibited from touching or tampering with any components of this device to prevent accidents.

5) Personnel responsible for the installation and commissioning of the equipment shall be familiar with the equipment’s basic structure, operating principles, performance characteristics, and sequence of operations, as well as the basic structure and operational status of each component.

6) Routine maintenance and servicing shall be carried out in strict accordance with the operating procedures to prevent accidental discharge of the extinguishing agent.

7) The air in the protected area shall not contain flammable or conductive dust, nor any harmful substances that could corrode components; otherwise, appropriate protective measures must be implemented, and the equipment must be safeguarded against vibration and impact.

8) Before the system discharges the extinguishing agent, all personnel must evacuate the fire area during the delay period (adjustable from 0 to 30 seconds). After extinguishing is complete, the ventilation fan must be started first to exhaust the waste gases before personnel are permitted to re-enter the site.

9) If a leak is detected in the cylinder bank, promptly notify qualified personnel for inspection and repair. Unauthorized refilling by non‑qualified personnel is strictly prohibited; any resulting consequences shall be borne by the responsible party.

10) Other safety measures shall comply with relevant national standards.

Appendix A: Minimum Design Extinguishing Concentrations for Selected Combustible Substances

Table A: Minimum Design Extinguishing Concentrations for Selected Combustible Substances

 

Name of Combustible Substance

Minimum Design Fire Extinguishing Concentration

Name of Combustible Substance

Minimum Design Fire Extinguishing Concentration

Acetone

9.1%

Hydraulic oil

8.0%

Acetonitrile

8.4%

Hydrogen

17.4%

Pentanol

9.6%

Isobutanol

10.0%

Benzene

8.0%

Isopropyl alcohol

9.9%

Butane

8.7%

JP4 aviation fuel

9.1%

Butanol

10.0%

JP5 aviation fuel

9.1%

Diethylene glycol

9.8%

Kerosene

9.8%

Dibutoxyacetate

9.1%

Methane

8.0%

Butyl acetate

9.2%

Methanol

13.7%

Carbon disulfide

15.6%

Methoxyethanol

12.4%

Chloroethane

8.3%

Methyl isobutyl ketone

9.8%

Crude oil

8.6%

Methyl ethyl butyl ketone

9.2%

Cyclohexane

9.5%

Solvent oil

8.7%

Cyclohexylamine

8.8%

Morpholine

10.4%

Cyclopentanone

9.8%

Nitromethane

13.1%

Dichloroethane

8.0%

Pentane

9.0%

Diesel fuel

8.8%

Propane

8.8%

Diethyl ether

9.9%

Propanol

10.2%

Ethane

8.8%

Propylene

8.2%

Ethanol

11.0%

Propylene glycol

11.4%

Ethyl acetate

9.3%

Pyrrolidine

9.6%

Ethylbenzene

8.3%

Tetrahydrofuran

9.8%

Ethylene

11.1%

Tetrahydrothiophene

8.7%

Ethylene glycol

10.0%

Toluene

8.0%

Gasoline

9.1%

Tolyl polyester

8.0%

Heptane

8.0%

Transformer oil

9.6%

Hexene

8.0%

Xylene

8.0%

 

Appendix B: Minimum Design Inerting Concentrations for Selected Flammable Substances

Table B: Minimum Design Inerting Concentrations for Selected Flammable Substances

 

Name of Combustible Substance

Minimum Design Inerting Concentration

1-Butane

11.3%

1-Chloro-1,1-difluoroethane

2.6%

1,1-Difluoroethane

8.6%

Difluoromethane benzene

3.5%

Ethylene oxide

13.6%

Methane

8.0%

Pentane

11.6%

Propane

11.6%

 

Single-Cabinet Type Heptafluoropropane Fire Suppression System | Frequently Asked Questions

 

Q1: What types of facilities are suitable for single-cabinet-type heptafluoropropane fire suppression systems?

A1: Suitable for enclosed protected areas such as small and medium-sized computer rooms, distribution rooms, archives, and energy storage compartments; effective for extinguishing electrical fires, but not suitable for fires involving reactive metals or strong oxidizers.

Q2: What is the difference between a single-cabinet type and a double-cabinet type?

A2: The single-cabinet type integrates the fire-extinguishing agent cylinder assembly and the initiating components into a single cabinet, occupying less floor space. It is suitable for applications with limited protected areas and relatively small extinguishing-agent requirements.

Q3: What startup methods does the device support?

A3: It supports three start-up modes—automatic interlock start, on-site manual start, and mechanical emergency start—meeting the requirements of fire safety codes.

Q4: Will the equipment be damaged after a heptafluoropropane discharge?

A4: The agent is clean and leaves no residue, does not corrode electrical equipment, and the equipment can be put back into service after ventilation following fire suppression.

Q5: What are the inspection cycles for pharmaceuticals and gas cylinders?

A5: The chemical agent exhibits stable performance and can be used continuously under normal operating conditions; steel cylinders must undergo a hydrostatic pressure test every three years, and may only be reused if they pass.

Q6: Do large gaps in the doors and windows of the protected area affect the fire suppression effectiveness?

A6: It has an effect. During fire suppression, the ventilation openings and doors and windows of the protected area must be closed to prevent the extinguishing agent from escaping and to ensure that the required extinguishing concentration is maintained.

Q7: During the system’s delayed‑release phase, may personnel remain inside the protected area?

A7: No. Personnel must evacuate the protected area within the delay period, and entry is strictly prohibited after discharge to prevent asphyxiation.

Q8: Can the heptafluoropropane agent be disassembled, reassembled, and refilled independently?

A8: No. Refilling of fire‑extinguishing agents and system maintenance must be performed by a qualified fire‑protection contractor; unauthorized operations may render the system inoperable.

Q9: Can a single cabinet‑type heptafluoropropane system protect multiple protected zones?

A9: It can be configured with a selection valve to protect multiple protected zones; when no selection valve is installed, it can only protect a single protected zone.

Q10: What routine maintenance checks should be performed?

A10: Regularly check the pressure gauge readings, inspect the cabinet for rust or deformation, and monitor the alarm control panel’s operating status; have the system inspected annually by a qualified maintenance provider.

Related Products


Inquiry Price

We attach great importance to your opinions and consultations. If you have any questions about our products and services, please fill out the following form, and we will contact you as soon as possible.