Rack-mounted perfluorohexanone fire suppression system
Keywords:
Category:
Detailed Description
Product Overview of Rack-Mounted Perfluorohexanone Fire Suppression Systems
Technical Parameter 1: Temperature-sensing model / Electric-start model
Name
Model number
| Instruction Manual for Rack-Mounted Gas Fire Suppression System YF8 ( 3、4 ) /2.5N-Y-ZY
| (Rack mounted) Prefabricated Perfluorohexane Fire Extinguishing Device
F8 ( 3、4 ) /2.5N-Y-ZY
|
Implementation Standard Execution standards | T/CESC 10171-2022 | T/CESC 10171-2022 |
Fire extinguishing agent name Agent name | Perfluorohexanone/Heptafluoropropane | 1230(FK5112)/227ea |
Total amount of extinguishing agent Dosage of medication | Up to 5k /Up to 4 kg | Maximum 5k/Maximum 4kg |
Fire-extinguishing agent driving method | Stored-pressure type (Pressure 1.6 MPa) | Storage pressure (pressure 1.6MPa) |
Startup Method (Standard Configuration) | Thermally induced 68℃ (expandable with DC 24V start-up) | Heat induced 68 ℃ (Expandable DC24V) |
Startup Method (Optional) | Electrical ignition (DC 24 V) 0.6A) 3s | Electric trigger (DC24V 0.6A) for 3 seconds |
Electric-start fire detection (optional) | Multi‑parameter composite detection, including temperature, smoke, and flame (with built-in analog smoke and temperature sensing) | Multiple composite detectors for temperature, smoke, flames, etc |
Injection time | <10S | <10S |
Operating temperature range | -10℃~50℃( Exceeds the requirement for customization) | -10 ℃~50 ℃ (customized for exceeding) |
External dimensions | 2U standard chassis (485 mm long × 385 mm wide × 89 mm high) | 2U standard chassis (length 485mm * width 385mm * height 89mm) |
Audio-visual alarm (standard configuration) | Built-in 12V 40 decibels | Built in 12V 40dB |
Audio-visual alarm (optional) | External DC 24V 80 decibels | External DC24V 80dB |
Output | Digital output, 1 channel (Normally Open) | Switch quantity 1 channel (normally open) |
Input (Electric Start) | Route 1 | 1 Road |
Case material | Q235 Powder coating 1.0 mm thick | Q235 spray coating thickness 1.0mm |
Panel material | Aluminum oxidation 3 mm thick | Aluminum oxide thickness 3mm |
Install the support plate. | 2 items | 2 pieces |
Mounting screws | Standard rack-mount screws | Standard rack mounting screws |
Spray mouth | Aluminum material Atomizing nozzle | Aluminum atomizing nozzle |
Whether to integrate with other platforms | Digital input RS485 Various communication protocols, including TCP | Aluminum atomizing nozzle switch quantity connection |
Technical Parameter 2: Non-pressurized Type (Atmospheric Pressure Type)
Name
Model number
| Instruction Manual for Rack-Mounted Gas Fire Suppression System F8 ( 3、4 ) /2.5N-Y-ZY
| (Rack mounted) Prefabricated Perfluorohexane Fire Extinguishing Device
F8 ( 3、4 ) /2.5N-Y-ZY
|
Implementation Standard Execution standards | T/CESC 10171-2022 | T/CESC 10171-2022 |
Fire extinguishing agent name Agent name | Perfluorohexanone | 1230(FK5112) |
Total amount of extinguishing agent Dosage of medication | Up to 2 kg | Maximum 2kg |
Fire-extinguishing agent driving method | Gas-generator-driven | Gas generator driven |
Startup Method (Standard Configuration) | Thermal start at 170°C and electric start | Gas generator driven thermal and electrical starting |
Fire detection | Multi‑parameter composite detection of temperature, smoke, flame, and more | Multiple composite detectors for temperature, smoke, flames, etc |
Injection time | <10S | <10S |
Operating temperature range | -10℃~50℃( Exceeds the requirement for customization) | -10 ℃~50 ℃ (customized for exceeding) |
External dimensions | 2U standard chassis (485 mm long × 385 mm wide × 89 mm high) | 2U standard chassis (length 485mm * width 385mm * height 89mm) |
Audio-visual alarm (standard configuration) | Built-in 12V 40 decibels | Built in 12V 40dB |
Audio-visual alarm (optional) | External DC 24V 80 decibels | External DC24V 80dB |
Output | Digital output, 4 channels (Normally Open) | Switch quantity 1 channel (normally open) |
Input | 4 lanes | 4 Road |
Case material | Q235 Powder coating 1.0 mm thick | Q235 spray coating thickness 1.0mm |
Panel material | Aluminum oxidation 3 mm thick | Aluminum oxide thickness 3mm |
Install the support plate. | 2 items | 2 pieces |
Mounting screws | Standard rack-mount screws | Standard rack mounting screws |
Spray mouth | Aluminum material Atomizing nozzle | Aluminum atomizing nozzle |
Whether to integrate with other platforms | Digital signal RS485 or other customizations | RS485 or other customized switch quantity |
Pharmaceutical Leakage Detection | Equipped with online monitoring functionality. | YES |
Electric start Functional block diagram

■Advantages and Features
● Safe and efficient
Extinguishing concentration ( 4.5~5.8% ) lower than NOAEL 10% , safety And efficient.
● Environmental protection
Ozone depletion potential of perfluorohexanone fire suppressant The layer damage value is 0 (ODP=0). ), The atmospheric residence time is 3–5 days, and the global warming potential (GW) P <1 ), The product’s environmental performance complies with the world’s most stringent environmental regulations. Requirements.
● Excellent insulation properties
Relative dielectric strength 2.3 (1 atm N 2 =1 ), Dielectric strength 10kV , with excellent insulation properties.
● Clean and residue-free
No residue remains after use and it will not damage electrical equipment. , causing damage to network servers, etc.
● Simple and convenient installation
It features a standard chassis enclosure that is robust and durable, with an overall sleek and elegant appearance.
■Typical Application Areas
●Data Center
●Network Server Room
●Communication base station
●Monitoring Center
●Digital Archive
● Energy storage device

Rack-Mounted Perfluorohexanone Fire Suppression System | Frequently Asked Questions
Q1: What types of facilities are suitable for rack-mounted perfluorohexanone fire suppression systems?
A1: Suitable for use in server cabinets, energy storage cabinets, communication racks, and other enclosed spaces to extinguish initial electrical fires inside cabinets; not suitable for fires involving reactive metals or strong oxidizers.
Q2: What are the key features of a rack-mounted perfluorohexanone fire suppression system?
A2: Designed for standard rack mounting, it features a compact footprint and can be installed directly inside the rack, enabling precise agent discharge at the exact location of a fire within the cabinet.
Q3: What startup methods does the device support?
A3: Features automatic activation via heat-sensing detection and can be linked to the fire alarm system for coordinated activation; some models are equipped with a manual emergency start function.
Q4: Will the discharge of perfluorohexanone extinguishing agent damage servers and other precision equipment?
A4: The agent is clean and leaves no residue, exhibits excellent insulating properties, does not corrode electronic components, and allows the equipment to be inspected and restored to service after ventilation.
Q5: How long is the shelf life of the medication, and does the vial need to undergo a hydrostatic pressure test?
A5: The formulation is chemically stable; pressurized‑type cylinders undergo hydrostatic testing in accordance with applicable standards, while non‑pressurized models do not require cylinder hydrostatic testing and have components replaced upon expiration.
Q6: Will leaving the cabinet vents open affect the fire suppression performance?
A6: Yes. During fire suppression, keep the cabinet’s ventilation openings closed as much as possible to minimize agent leakage and ensure that the interior of the cabinet reaches the designed extinguishing concentration.
Q7: When the system is activated and releases the extinguishing agent, can personnel approach the cabinet?
A7: Do not approach. After discharge, do not open the cabinet immediately to avoid inhaling the agent’s vapors; wait until adequate ventilation has been achieved before proceeding.
Q8: Can the perfluorohexanone agent be disassembled, reassembled, and refilled independently?
A8: No. Refilling of fire‑extinguishing agents and equipment maintenance must be performed by a qualified fire‑safety contractor; unauthorized operations may render the system inoperable.
Q9: Can a rack-mounted device protect multiple cabinets?
A9: For standard applications, each unit corresponds to a single cabinet; if multiple cabinets require protection, a piped‑network system can be used for centralized protection.
Q10: What routine maintenance checks should be performed?
A10: Regularly inspect the securement of the equipment and the integrity of the detection components, and check the cylinder‑group pressure; have it tested annually by a qualified maintenance provider.